Product Overview
Reliable ame detection and burner-to-burner discrimination in
multi-burner boilers is signicantly more challenging with the NFPA 85
requirement to prove “ame not detected” prior to burner start-up. is
NFPA requirement along with dicult discrimination challenges, such as
low NOx burners and opposed red boilers, are demanding more powerful
signal analysis and tuning capability from ame detection systems. e
IDD 9000 employs a Digital Signal Processor (DSP) based ame signal
processing method to oer advanced tuning capabilities necessary for a
NFPA compliant system.
e IDD 9000 Flame Amplier is designed for easy upgrade of
existing Forney ame ampliers with most installations simply requiring a
ame amplier replacement and reconnection of existing wires to improve
ame detection and discrimination. e IDD 9000 is available in panel
or rack mount; single or dual channel congurations. e dual channel
congurations use two fully independent channels to support two ame
detectors simultaneously.
Compatibility
• Amplier Upgrades - e IDD 9000 can replace most Forney ame
ampliers, panel or rack mount, in any application with complete
compatibility.
• Flame Detector - Works with all versions of Forneys IDD and UV-4
detectors.
• Analog Output - Flame intensity output is available in either
0-10 VDC or 4-20 mA.
IDD 9000 Flame Detector Amplier
• Enhanced Discrimination and Tuning -
Increased IDD frequency response options
along with spectrum weighting capability
for tuning to unique ame patterns.
• Storage for eight operating proles allows
BMS controlled or manual le switching
for instantaneous recall of optimized
performance for a variety of fuels and
burner operating conditions.
• Flame signal processing can be IR only or
UV only on each channel.
• Connecting an IDD and UV-4 ame
detector to one dual channel IDD 9000
amplier allows supervision of a burner/
igniter pair.
Factory Mutual Approved
• Factory Mutual (FM) approval means safe
operation and lower insurance rates
e IDD 9000 Flame Detector Amplier
provides enhanced discrimination and
tuning for NFPA compliant systems and
oers a single retrot solution for multiple
discrete legacy ampliers.
Features & Benets
A UTC Fire & Security Company
Forney Corporation • 3405 Wiley Post Road • Carrollton, TX 75006 • 800-356-7740 • Fax 972-458-6650 • www.forneycorp.com
IDD9000rev11-2011_PM & RM.indd 1 11/15/2011 4:59:28 PM
Vue de la page 0
1 2

Résumé du contenu

Page 1 - Features & Benets

Product Overview Reliable ame detection and burner-to-burner discrimination in multi-burner boilers is signicantly more challenging with the NFPA 8

Page 2 - IDD 9000 Specications:

add 7/8” for mating connectorsThe PM IDD 9000 is available as single or dual channel. The dual channel has a separate, identical PCB motherboard for

Commentaires sur ces manuels